תנור אוויר חם תעשייתי Tecnoclima PMX - Warm Air Heaters

                                       Direct diffusion suspended version

PMX - premix condensing unit heaters for indoor suspended installation with direct air diffusion into the environment (axial fan).

 Tecnoclima premix gas suspended warm air heaters have many advantages:

  • heat capacity of the premix burner has a wide modulation range: from 100% to 30% of the nominal heat capacity;
  • thanks to the modulation of the thermal capacity, as the demand for heat from the environment decreases, very high efficiency values are reached, up to 106%, with many benefits in terms of environmental comfort and the reduction of gas consumption;
  • the premix burner allows perfect mixing of the gas with the combustion air obtaining a semi-radiant flame band with very low emissions of nitrogen oxides, NOx: Class 5 of emissions
  • very high thermal efficiency and progressive modulation of the thermal power contribute to obtain operating cost savings of over 30% compared to traditional systems.
Description
Diemensions
Technical features


Condensing sealed warm air heaters with modulating premix gas burner, PMX range, are designed to be installed inside the environment and to diffuse the air directly into the environment to be heated. The PMX heaters has a diffuser panel with fins that are individually adjustable (vertically and orizontally)to direct the flow of warm air into the environment. The axial fans adopt motors with high energy efficiency and silent operation. The unit operates with variable thermal power with continuous modulation, fully automatically regulated from the remote control panel with integrated or remote environment temperature probe. The warm air heaters, thanks to the continuous modulation of the thermal capacity, decreases automatically the heating power, reaching performance values of up to 106%, consuming less fuel and ensuring ideal comfort and significant overall operating economy.
The PMX warm air heaters finds application in the heating of industrial and commercial environments, facilities for sports, entertainment, etc.
Model Overall dimensions mm Ø Flue gas exhaust, mm Ø Combustion air intake, mm Gas inlet, inches Weight Kg
A B C
PMX 30 885 830 580 80 80 1/2” G 65
PMX 40 885 830 580 80 80 1/2” G 75
PMX 50 1225 896 650 80 80 1/2” G 90
PMX 60 1225 896 650 80 80 1/2” G 95
PMX 90 1775 1081 800 100 100 3/4” G 205
PMX 120 1775 1081 800 100 100 3/4” G 215
  • PMX
  • PMX
  • PMX
Model U.M. PMX 30 PMX 40 PMX 50 PMX 60 PMX 90 PMX 120
Max Min Max Min Max Min Max Min Max Min Max Min
Thermal capacity 1 (input) kW 29,1 9,4 38,5 13,3 49,8 18,4 59,0 20,0 90,8 33,3 116,0 40,6
kcal/h 25.057 8.075 33.111 11.456 42.822 15.833 50.745 17.184 78.102 28.612 99.760 34.887
Thermal capacity 1 (output) kW 28,0 10,0 37,0 14,0 48,0 19,0 57,0 21,0 89,0 35,0 115,0 43,0
kcal/h 24.080 8.600 31.820 12.040 41.280 16.340 49.020 18.060 76.540 30.100 98.900 36.980
Total efficiency2 % 96,1 106,5 96,1 105,1 96,4 103,2 96,6 105,1 98,0 105,2 99,1 106,0
Condensate produced3 l/h 0,2 1,1 0,3 1,3 0,3 1,5 0,3 1,9 1,6 3,3 2,7 4,3
Nominal airflow rate m3/h 3.200 4.400 5.500 6.500 10.000 13.000
Air temperature increase (Δt) K 26 9 25 9 26 10 26 10 26 10 26 10
Class NOx4   5
Electrical power supply V/Hz Monofase 230/50/1 Trifase 400/50/3N
Sound pressure (Lp)5 dB(A) 53 55 56 57 56 60
Air throw distance6 m 20 28 32 35 39 42
Max instantaneous consumption1
Methane G20
Methane G25
Propane G31
 
Nm3/h 3,1 1,0 4,1 1,4 5,3 1,9 6,2 2,1 9,6 3,5 12,3 4,3
Nm3/h 3,6 1,2 4,7 1,6 6,1 2,3 7,3 2,5 11,2 4,1 14,3 5,0
Nm3/h 1,2 0,4 1,6 0,5 2,0 0,8 2,4 0,8 3,7 1,4 4,7 1,7

 

(1) Methane gas G20: Hi = 34,02 MJ/Nm3
 Methane gas G25: Hi = 29,25 MJ/Nm3
 Propane gas G31: Hi = 88,00 MJ/Nm3
(2) Referring to a lower heating power (Hi) with latent heat recovery.
(3) Indicative variable value depending on the environmental conditions.
(4) Reference Standard UNI EN 1020 with methane gas G20.
(5) Measured in free field at a distance of 6 metres.
(6) Referred to air temperature +20°C – residual speed 0.2 m/s.
Control
 

Suspended heaters PMXCMX and MIXIJET are operated by a dedicated remote control panel. For each installation it is necessary to provide a remote command to set and control the operation of one or several heaters.

 

The remote control panel integrates in a single interface in addition to the functions of ambient thermostat, also those of remote control of the heating system, allowing cascade management of up to 10 heaters with a single control device. Through the remote panel it is possible to manage the operating parameters, display diagnostic messages and reset the heaters if necessary.

 

The control panel allows setting of different thermoregulation modes by integrating ambient probes and external probes. Weekly programming is simple and allows adapting of the system to different installation and seasonal requirements. The graphic display allows to view intuitively daily operating programs.

Original accessories
 
Fuel gas exhaust and combustoon air intake
Installation systems that comply with the regulations for gas appliances with an “Open” (type B) or “Sealed” (type C) combustion circuit. The current regulations require gas appliances installed according to one of the following five types of exhaust gas and combustion air ducts, which are indicated by the abbreviations: B23 - B23P - C13 - C63 - C33. The drawings represent the gas appliance with a axial fan, but the same concept applies to the version with centrifugal fan.
The gas appliance must be connected to a single duct that brings combustion products outside of the room. The combustion air is taken directly from the appliance installation area.
The gas appliance has two ducts, one for the discharge of the combustion products and the other for the intake of combustion air, both communicating with the environment outside the installation room. The outlet must be wall-mounted with two separate ducts or with two coaxial ducts.
The gas appliance must be connected to two separate ducts communicating with the outside. The one to discharge the products of the combustion through the roof while the other one for the combustion air intake through the wall.
The gas appliance must be connected to two ducts, one for the discharge of the combustion products and the other for the intake of combustion air with a coaxial terminal communicating with the environment outside the installation environment, from the roof.
NOTES:
For information on materials and the selection of exhaust flue gas and combustion air intake accessories, refer to the specific technical document which shows the diagrams and installation examples.